Calculation of air conditioning chilled water flow rate | How to calculate the amount of central air conditioning cooling (chilled) water retention?

flowmeter01956

DateTime 08/05/2026 Show 159

『Calculation of chilled water flow rate for air conditioning』Related information(v cone flow meter|rotary gas meter|gallon meter|gear meter|metal tube rotameter|glass tube rotameter|nutating disk meter|transit time ultrasonic flow meter|wedge flow meter|pd meters|hydraulic flow meter|ultrasonic water flow meter|water flow meter|air flow meter|magnetic water flow meter|oxygen flow meter|gas flow meter|argon flow meter|air velocity meter|gasoline flow meter|fuel flow meter|ultrasonic water meter|digital water meter|nitrogen flow meter|solid flow meter|Oxygen tank flow meter|digital water flow meter|diesel fuel flow meter|steam flow meter|02 flow meter|compressed air flow meter|oil flow meter|liquid flow meter)

How to calculate the terminal cooling load of central air conditioning under the conditions of 1... and chilled water flow rate?

The formula for calculating the terminal cooling load of central air conditioning is: q=1000m * c * (T2-T1). In this formula, q represents the cooling load in watts (W), m is the flow rate of chilled water in kilograms per second (kg/s), and c is the specific heat capacity of chilled water, typically taken as 4.18 kilojoules per kilogram per degree Celsius (kJ/(kg * ℃)). T1 and T2 are the supply and return water temperatures of chilled water, respectively, measured in degrees Celsius (℃). Specifically, this formula can help us calculate the amount of cooling that a central air conditioning system can provide under specific conditions. For example, if we know that the supply and return water temperatures of chilled water are 7 ℃ and 12 ℃ respectively, and the flow rate of chilled water is 0.1 cubic meters per second, we can calculate the cooling load using the above formula. Firstly, I need to convert the flow rate of chilled water from cubic meters per second to kilograms per second. Given that the mass of 1 cubic meter of water is approximately 1000 kilograms, a chilled water flow rate of 0.1 cubic meters per second is equal to 100 kilograms per second. Next, we can substitute the known values into the formula for calculation: q=1000 * 100 * 4.18 * (12-7)=2.09 * 10 ^ 6 W. After calculation, it can be concluded that the cooling load at the end of the central air conditioning system is 2.09 megawatts (MW). This value can help us grasp the cooling capacity of the system under specific conditions, providing a basis for equipment selection, operation management, and maintenance. It is wo

Calculation of chilled water flow rate for air conditioning
rth noting that in practical applications, various factors that affect cooling load may be encountered, such as equipment efficiency, pipeline thermal high key loss, etc. Therefore, in specific calculations, the impact of these factors on cooling load should also be considered. In addition, different types of central air conditioning systems may require different calculation methods and parameters, so relevant technical specifications and standards should be referred to in practical applications. In summary, through the above formula, we can accurately calculate the cooling load at the end of the central air conditioning system, which is of great significance for optimizing system operation and improving energy efficiency.

2. Simple calculation of water flow rate in air conditioning water system

The simple calculation method for water flow rate in air conditioning water system is as follows:

1. Calculation of cooling water flow rate The calculation of cooling water flow rate is usually based on the cooling capacity of the refrigeration unit and considers a certain safety factor.

. The specific calculation formula is as follows: L (m3/h)=[Q (kW)/(4.5~5) ℃ × 1.163] × (1.15~1.2) Q (kW): the cooling capacity of the refrigeration host

4.5~5 ℃: represents the temperature difference between the inlet and outlet of the cooling water, usually calculated within this range. 1.163: The product of physical parameters such as density and specific heat capacity of water, used for unit conversion. (1.15~1.2): To ensure sufficient cooling water flow for safety reasons. In practical applications, the cooling water flow rate can be directly selected based on the values provided by the product sample, or calcul